How do earthing and a residual current device (RCD) work? Why does it trip?

Most 'the breaker trips when I turn on the water heater' faults aren't the breaker at all, but the RCD. One idea is enough to understand when and why it trips: if the current going out doesn't come back, it's leaking somewhere.

What does it do? A residual current device (RCD, also called an RCCB or GFCI) passes the L and N conductors together through a toroid. In a healthy circuit the outgoing and returning currents are equal and their fields cancel. If some current leaks to earth through the frame and PE, or through a person's body, a difference (IΔ) appears between L and N; once it exceeds 30 mA the RCD opens L and N together within 300 ms at most, within 40 ms at 150 mA. An RCD doesn't limit the current, it limits the time; nor does it protect against overcurrent. Earthing (PE) holds the frame at earth potential in a fault and gives the leak a far easier path than a body. Together they protect you.